Programming
Engineer Menu 1
Engineersmenu 1isselectedwhen theengineer'spasscode is enteredduringthe unsetcondition.
The engineer may leave engineer menu 1 by pressing the [ESC] key. The system will return to the
unset condition butt he remotekeypads willshow: "ENG ON SI TE". T his message will be clear ed the
next time a valid user passcode is entered. When engineers mode is selected the monitoring of
tamper circuits is disabled.
Panel Outputs
Outputs1to4 forthecontrolpanel and5 to 8 fortheremotekeypadscanbeprogrammedtoany
of the output functi on types 0 to 55 as listed in Table 2 on page 15.
1. Ensure that "Engineer Menu 1 " is selected .
2. Press 1 to select the Panel Outpu ts option.
3. The display will show: PAN.-
4. Enter the required output number 1 to 8.
5. The display will show the current output function (Table 2).
6. Enter the new function num ber and press [.
7. The display will return to step 3. Repeat steps 4 to 7 for the
remaining outputs.
8. Press ] to return to "Engineer Menu 1".
Digicom Outputs
The eightswitched-veDigicomoutputs1 to 8 may beconn ectedto theDigic om channelinputs.
The outputs may be programmed to any of the function types 0 to 55 (Table 2).
1. Ensure that "Engineer Menu 1 " is selected .
2. Press 2 to select the Digicom Outputs option.
3. The display will show: DIG.-
4. Enter the required digicom ou tput number 1 to 8.
5. The display will show the current output function (Table 2).
6. Enter the new function num ber and press [.
7. The display will return to step 3. Repeat steps 4 to 7 for the
remaining d igicom outputs.
8. Press ] to return to "Engineer Menu 1".
Plug-on Digicom Channels
The eight channels for t he plug-on digicom may be programmed to any of the function types 00
to 55 (Table 2). The procedure is similar to programming the digicom ou tputs (above).
1. Follow above procedure, except press 3 at st ep 2.
16
Programming TS700 Installation Manual
PAN.-
Ent er panel output 1 - 4 or
remote output 5 - 6.
04
Ent er new output type 00 - 55
(see Table 2 .)
DIG.-
Ent er digicom output 1 - 8.
04
Ent er new output type 00 - 55
(see Table 2 .)
Dc3.-
Ent er digicom output 1 - 8.